What is the voltage drop?
Pick the wire metal and AWG size, type the supply voltage, the load current and the one-way length. The voltage drop calculator shows the volts lost in the wires, the percent drop and the voltage left at the load.
- Voltage drop
- 7.73 V
Over 100 ft of 12 AWG wire at 20 A, the voltage drop is 7.73 V (6.44% of 120 V), leaving 112.27 V at the load.
- Voltage drop, percent
- 6.44%
- Voltage at the load
- 112.27 V
- Resistance, Ω per 1,000 ft
- 1.9316
- Resistance, Ω per km
- 6.3371
- Diameter, inches
- 0.0808
- Area, mm²
- 3.309
Voltage drop: 7.73 V. Over 100 ft of 12 AWG wire at 20 A, the voltage drop is 7.73 V (6.44% of 120 V), leaving 112.27 V at the load.
How to calculate
Computes the voltage drop, the percent drop and the voltage at the load for a copper or aluminium circuit, from the AWG wire size, the one-way length, the current, the supply voltage and the conductor temperature.
Example with the default inputs (Conductor Copper, Wire size (AWG) 12 AWG, Circuit DC or single-phase, Supply voltage 120 V, Load current 20 A, One-way length 100 ft, Conductors in parallel 1, Conductor temperature 75 °C): Over 100 ft of 12 AWG wire at 20 A, the voltage drop is 7.73 V (6.44% of 120 V), leaving 112.27 V at the load.
Method: d = 0.005 in × 92^((36 − n) ÷ 39); R = ρ₂₀ × (1 + α × (T − 20 °C)) ÷ (π d² ÷ 4); drop = k × L × I × R ÷ conductors in parallel, with k = 2 (DC or single-phase) or √3 (three-phase).
- Solid round wire at the AWG diameter; stranded wire of the same gauge has a little more resistance.
- Copper is annealed copper of 100% IACS, 1/58 Ω·mm²/m at 20 °C with α = 0.00393; aluminium is 61% IACS, 0.028264 Ω·mm²/m with α = 0.00403.
- AC circuits count resistance only: no inductive reactance, skin effect or power factor, which add a little drop in large wires.
- The load draws the typed current whatever the voltage at its end.
Worked examples
Each example is checked against the calculator on every build.
- Conductor Copper, Wire size (AWG) 12 AWG, Circuit DC or single-phase, Supply voltage 120 V, Load current 20 A, One-way length 100 ft, Conductors in parallel 1, Conductor temperature 20 °C gives Resistance, Ω per 1,000 ft 1.588, Diameter, inches 0.0808.Source: NBS Handbook 100, Copper Wire Tables (1966), Table 1: 12 AWG, 80.8 mils, 1.588 Ω per 1,000 ft at 20 °C
- Conductor Copper, Wire size (AWG) 10 AWG, Circuit DC or single-phase, Supply voltage 120 V, Load current 20 A, One-way length 100 ft, Conductors in parallel 1, Conductor temperature 20 °C gives Resistance, Ω per 1,000 ft 0.9989.Source: NBS Handbook 100, Copper Wire Tables (1966), Table 1: 10 AWG, 0.9989 Ω per 1,000 ft at 20 °C (rounded table value)
- Conductor Copper, Wire size (AWG) 12 AWG, Circuit DC or single-phase, Supply voltage 120 V, Load current 20 A, One-way length 100 ft, Conductors in parallel 1, Conductor temperature 75 °C gives Resistance, Ω per 1,000 ft 1.931555, Voltage drop 7.73 V, Voltage drop, percent 6.438518%, Voltage at the load 112.27 V.Source: ASTM B258 diameter formula
- Conductor Aluminium, Wire size (AWG) 4/0 AWG, Circuit Three-phase, Supply voltage 480 V, Load current 200 A, One-way length 250 ft, Conductors in parallel 1, Conductor temperature 75 °C gives Diameter, inches 0.46, Voltage drop 8.5 V, Voltage drop, percent 1.770972%.Source: ASTM B258 (4/0 AWG = 0.4600 in)
- Conductor Copper, Wire size (AWG) 6 AWG, Circuit DC or single-phase, Supply voltage 230 V, Load current 32 A, One-way length 98.43 ft, Conductors in parallel 1, Conductor temperature 75 °C gives Resistance, Ω per km 1.57634, Voltage drop 3.03 V, Voltage drop, percent 1.315901%.Source: ASTM B258
How it works
- Diameter of AWG size n (ASTM B258): d = 0.005 in × 92^((36 − n) ÷ 39), for every size from 20 AWG to 4/0. The sizes 1/0, 2/0, 3/0 and 4/0 are n = 0, −1, −2 and −3.
- Cross-section: A = π × d² ÷ 4.
- Resistance per metre at conductor temperature T: R = ρ₂₀ × (1 + α × (T − 20 °C)) ÷ A.
- Copper: ρ₂₀ = 1/58 Ω·mm²/m = 1.7241 × 10⁻⁸ Ω·m, α = 0.00393 per °C.
- Aluminium: ρ₂₀ = 0.028264 Ω·mm²/m, α = 0.00403 per °C.
- Voltage drop = k × L × I × R ÷ N, where L is the one-way length, I the current, N the conductors in parallel per leg, and k = 2 for DC or single-phase AC or √3 for three-phase AC (with the line-to-line voltage).
- Percent drop = drop ÷ supply voltage × 100; voltage at the load = supply − drop.
The page also shows R per 1,000 ft and per km, the diameter in inches, and the cross-section in mm², for one conductor at T. Temperatures in °F are converted exactly: °C = (°F − 32) ÷ 1.8.
No answer. When the drop would be the whole supply voltage or more, the calculator shows: "The voltage drop would be the whole supply voltage or more: use a larger wire, a shorter run or less current."
Rounding. Volts show with at most 2 decimals, the percent drop with 2, resistances and the diameter with 4, the cross-section with 3, rounded half up, with trailing zeros left off.
Assumptions
- Solid round wire at the AWG diameter; stranded wire has a little more resistance.
- AC circuits count resistance only: no reactance, skin effect or power factor.
- The load draws the typed current whatever the voltage at its end.
- Supply up to 1,000 kV, current up to 100,000 A, length up to 100 km, 1 to 20 conductors in parallel, conductor temperature from −50 °C to 150 °C.
Worked examples by hand
12 AWG copper at 20 °C. d = 0.005 × 92^(24/39) = 0.08081 in = 2.0525 mm; A = 3.3088 mm². R = 0.017241 ÷ 3.3088 = 0.0052108 Ω/m = 1.5883 Ω per 1,000 ft (the wire table: 1.588).
10 AWG copper at 20 °C. d = 0.1019 in, A = 5.2612 mm², R = 0.9989 Ω per 1,000 ft.
A 20 A load 100 ft from a 120 V panel, 12 AWG copper at 75 °C. R = 1.5883 × (1 + 0.00393 × 55) = 1.9316 Ω per 1,000 ft. Drop = 2 × 100 × 20 × 1.9316 ÷ 1,000 = 7.73 V, which is 6.44%, leaving 112.27 V.
A three-phase 480 V, 200 A feeder, 4/0 aluminium, 250 ft, 75 °C. d = 0.46 in, A = 107.22 mm², R = 0.028264 × (1 + 0.00403 × 55) ÷ 107.22 = 0.00032204 Ω/m = 0.098157 Ω per 1,000 ft. Drop = √3 × 250 × 200 × 0.098157 ÷ 1,000 = 8.50 V = 1.77%.
A 32 A load 30 m from a 230 V supply, 6 AWG copper at 75 °C. A = 13.30 mm², R = 1.5763 Ω/km. Drop = 2 × 30 × 32 × 1.5763 ÷ 1,000 = 3.03 V = 1.32%.
Other questions people ask
How do I calculate voltage drop?
Multiply the wire’s resistance per foot by the length the current travels and by the current: VD = 2 × L × I × R for DC or single-phase AC, where L is the one-way length (the current goes out and back), and VD = √3 × L × I × R for three-phase. A 20 A load 100 ft away on 12 AWG copper at 75 °C (1.9316 Ω per 1,000 ft) loses 2 × 100 × 20 × 0.0019316 = 7.73 V.
What is an acceptable voltage drop?
The US National Electrical Code has a note, not a rule, that suggests at most 3% on a branch circuit and 5% in total from the service to the farthest outlet. On a 120 V circuit, 3% is 3.6 V. If the calculator shows more, try the next larger wire size.
How is the resistance of a wire found from its AWG size?
The AWG diameter is d = 0.005 in × 92^((36 − n) ÷ 39), where n is the gauge (1/0 is 0, 4/0 is −3). The cross-section is π × d² ÷ 4, and the resistance per length is the metal’s resistivity divided by that area. 12 AWG copper is 0.0808 in across and has 1.588 Ω per 1,000 ft at 20 °C, as the classic copper wire tables list.
Why does temperature matter?
Metals conduct worse when hot. Copper’s resistance rises by 0.393% for each °C above 20 °C, aluminium’s by 0.403%. Building wire rated 75 °C, used at that temperature, has about 22% more resistance than at 20 °C, so the calculator starts at 75 °C.
Does aluminium wire have more voltage drop than copper?
Yes, for the same size. Aluminium conducts about 61% as well as copper, so its resistance is about 1.64 times as high. That is why an aluminium conductor is usually one or two sizes larger than a copper one for the same load.
Why does this answer differ a little from the NEC tables?
The calculator uses the AWG formula for solid round wire and the resistivity of the metal, not the NEC Chapter 9 tables. Stranded conductors and coated wire in the tables have slightly more resistance, and AC tables add reactance. For solid 12 AWG copper at 75 °C the formula gives 1.93 Ω per 1,000 ft, the same as the table’s solid value.